Q
How to choose 3-pole and 4-pole ATS?
A

For the same type and capacity between the two power supply automatic conversion, such as two public power grid, two generator sets such as neutral line does not switch or common neutral line power can be used 3 poles; 4 poles are used for automatic conversion between power supplies of different systems and capacities.

1). If the grounding network between the normal power supply and the standby generator is not the same, the ATS uses 4 poles

2). ATS with residual current protection applies 4 pole, two power switches with residual current protection, and ATS with seven lower levels applies 4 pole

3). 4 pole ATS for power conversion between two different grounding systems

4). Tn-s and TN-C-S systems generally do not need to set 4 pole switches. However, the special case of TN-S system, such as three-phase serious imbalance, should be determined according to the importance of the building class.

Q
What is the difference between the two-position ATS model and the three-position ATS model?
A

Two position: ATS switch contact has only two working positions (normal power supply and standby power supply), one action in place, fast conversion time

Three position: ATS switch contact has three working positions (normal power supply and standby power supply, zero position), zero position switch main contact is in neutral, the main role when the high load is high reactance or large motor load, in order to avoid the impact of current for temporary stay.

Q
Whether an isolation device is required before the ATS?
A

The ATS is suitable for the automatic conversion of the primary power supply and the standby power supply in the power supply and distribution system of primary and secondary loads. To meet the requirements of the distribution system, the primary and secondary load distribution system should adopt the automatic mutual transfer of the two power supply ends. The ATS is usually installed at the incoming line side of the distribution box of the last stage of the distribution system. When the power supply needs to be disconnected for maintenance, testing and inspection of equipment, isolation appliances should be set up

Q
Is a short circuit protection device set before the ATS?
A

The CB class ATS body implements the thermal and magnetic protection of the circuit breaker itself. The main contact can be switched on and used for segmental short-circuit current. The front end can only be set with isolation appliances or isolation switches, without setting short-circuit protection appliances.

The PC-class ATS has only the power conversion function but no short circuit or overload protection function. Therefore, the front end of the PC-class ATS must meet isolation requirements for short circuit protection.

Q
What is the ATS conversion time?
A

The time of the conversion process from the moment of the final extinguishment of the arc of each phase to the closing of another power source by the main contact is measured, including the time delay introduced specially. General users should pay attention to "total action time" or "conversion action time" to meet the requirements of different power distribution systems.

The total operation time of two-position PC ATSE is generally 50 ~ 250ms.

The total operation time of three-position PC ATSE is generally 350 ~ 600ms;

The total operation time of CB ATSE is generally 2000-3000ms

Q
What is your warranty time?
A

18 Month

Q
Do you accept OEM or ODM order?
A

Yes, we provide OEM and ODM order ,in China more than 1000 company make OEM from us.

Q
What is your lead time?
A

Normally within 10 days. It depends on your Qty.

Q
What is your payment term?
A

T/T, LC, Western Union,Alibaba Trade Assurance is all acceptable.

Q
What kind of voltage of the ATS you can do?
A

110V, 220V, 380V, 400V, 415V

Q
What Current you can do?
A

16A-3200A

Q
How about the quality?
A

Our products is high quality,We strictly comply with ISO9001 and IEC60094 implementation.